Installation Procedure
(1) Make sure the probe in the tank is on the right side of the filter net, the filter net and
the upper cover are firmly mounted on the tank.
(2) Make sure the tank is placed smoothly and the outlet pipe of the air conditioner is
tightly connected with the water pipe of tank.
(3) Connect the vent pipe with the air hole.
(4) Place the pump in the position beyond the ceiling.
(5) The use of shockproof materials, ensure the water tank and condensate pump stuck
firmly, low vibration to avoid noise.
(6) Pay attention to the direction of the water flow.
(7) Connect the water tank and pump with 6x9 silicone tube and fasten it with tie, make
sure the length of the water pipe is less than 2m.
(8) Connect the 6x9 water pipe to the water outlet, tie the water pipe, make sure that
the discharge head is less than 8m and the length of the water pipe is less than
25m.
(9) The condensate pump is equipped with work indicating light. When the pump is
working normally, the green light is on. When the water level is in
alarm, the red light is on.
(10) Power supply wiring, in order to avoid leakage of condensate pump, please
connect the alarm signal line and the "Normally Closed" and "Normally Open"
signal terminals according to the requirements of different working conditions .